EKO_Q39_Infiltration Version 7.1.1

Modified on Wed, 29 Jan at 5:08 PM

REQUIRED PHOTO of Infiltration Test Results OR REPORT from Testing Software per ANSI/RESNET/ICC 301-2019 APPENDIX B and MINHERS Chapter 9. Raters/RFIs are responsible for documenting reasons for missing photos. Infiltration (Envelope Leakage) is tested according to ANSI/RESNET/ICC 380. The Rater/RFI should include sufficient documentation to support the leakage rate modeled. Ensure that test results are correctly applied and modeled based off testing method used (single point vs multi-point).

  • Examples include blower door manufacturer’s automated software report (TECTITE, FanTestic, TEC Auto Test app, etc.) and/or photo documentation.

SCORING:

"Satisfactory" when correct or "Unsatisfactory" when incorrect OR NO PHOTO.

GUIDANCE:

CFM50 - Field QA: QAD tested value within 10% of Rater/RFI value. File QA: At least one photo provided from Rater/RFI which shows test results OR Report from Testing Software.