REQUIRED PHOTO of Infiltration Test Results OR REPORT from Testing Software per ANSI/RESNET/ICC 301-2019 APPENDIX B and MINHERS Chapter 9. Raters/RFIs are responsible for documenting reasons for missing photos. Infiltration (Envelope Leakage) is tested according to ANSI/RESNET/ICC 380. The Rater/RFI should include sufficient documentation to support the leakage rate modeled. Ensure that test results are correctly applied and modeled based off testing method used (single point vs multi-point).
- Examples include blower door manufacturer’s automated software report (TECTITE, FanTestic, TEC Auto Test app, etc.) and/or photo documentation.
SCORING:
"Satisfactory" when correct or "Unsatisfactory" when incorrect OR NO PHOTO.
GUIDANCE:
CFM50 - Field QA: QAD tested value within 10% of Rater/RFI value. File QA: At least one photo provided from Rater/RFI which shows test results OR Report from Testing Software.
Was this article helpful?
That’s Great!
Thank you for your feedback
Sorry! We couldn't be helpful
Thank you for your feedback
Feedback sent
We appreciate your effort and will try to fix the article