PHOTO REQUIRED of above grade wall insulation per ANSI/RESNET/ICC 301-2019 APPENDIX B and MINHERS Chapter 9. Raters/RFIs are responsible for documenting reasons for missing photos. For above grade walls, confirm that the wall types, insulation types, insulation materials, insulation thicknesses, insulation grades, R-values, stud types, stud spacings/dimensions, framing factors, surface areas, surface colors and locations which are entered into the software correspond with plans and/or field data collected by the Rater/RFI for the actual condition of the rated home. For rim and band joists, confirm that the types, R-values, surface areas and locations which are entered into the software correspond with plans and/or field data collected by the Rater/RFI for the actual condition of the rated home.
- Be sure that where multiple above grade wall types exist or where multiple rim/band joists types exist they are handled separately, including where their “location” with respect to conditioned areas of the home may vary between wall/rim and band types and within the same wall/rim and band type.
SCORING:
- Satisfactory: No errors in modeling
- 1: one to two minor errors in modeling (listed below) (this is per modeled wall)
- 2: NO PHOTO OR three to four minor errors (listed below) in modeling OR one to two major errors in modeling (this is per modeled wall)
- 3: five or more minor errors (listed below) OR three or more major errors in modeling (listed below) (this is per modeled
GUIDANCE:
Minor AGW Modeling Errors:
- Incorrect Wall Construction modeled
- Insulation R-Value of each modeled AGW off by 5% to 10%
- Insulation thickness of each modeled AGW off by 0.5 to <1.0 inch
- Incorrect Gypsum thickness modeled
- AGW Surface Area of each modeled AGW off by 4% to 7%
- Incorrect Surface Color modeled
- Incorrect Insulation Location modeled
Major AGW Modeling Errors:
- Insulation R-Value of each modeled AGW off by greater than 10%
- Insulation thickness of each modeled AGW off by greater than 1.0 inch
- Incorrect Insulation Grade value modeled (based on ANSI/RESNET/ICC 301-2019 Appendix A - depth/void variance for insulation type and grade)
- Incorrect stud depth, spacing, or framing fraction modeled
- AGW Surface Area of each modeled AGW off by greater than 7%
Was this article helpful?
That’s Great!
Thank you for your feedback
Sorry! We couldn't be helpful
Thank you for your feedback
Feedback sent
We appreciate your effort and will try to fix the article