For each duct system, confirm that the system types, field test status, associated heating/cooling equipment, square feet served, # of returns, duct areas, duct insulation R-values, locations and % areas which are entered into the software correspond with field-verified plans and/or field data collected by the Rater/RFI for the actual condition of the rated home.
- Using rating software to estimate surface area is appropriate for most ducted systems. Any entered duct surface areas that deviate significantly from a software estimate (e.g. the small surface area of high-velocity ducts) should be documented in notes and/or photographs.
SCORING: Satisfactory: No errors in Duct System modeling 1: one to two minor errors in Duct System modeling (listed below) (this is per modeled system) 2: three to four minor errors (listed below) in Duct System modeling OR one to two major errors in Duct System modeling (this is per modeled system) 3: Incorrect number of Duct Systems OR five or more minor errors (listed below) OR three or more major errors in Duct System modeling (listed below) (this is per modeled system) N/A: No Duct/Distribution Systems in home.
GUIDANCE: Minor Duct Systems Modeling Errors:
- Duct System Square Feet Served off 2% to 5%
-
of Return Grills off by 1
- Supply and Return Duct Area if Measured or ACCA Manual D Sizing method is selected off by 2% to 5%
- Duct Location or Supply/Return percentages listed as correct location but incorrect condition (Attic, well vented vs Attic, well vented, under insulation) Major Duct Systems Modeling Errors:
- Incorrect field test status identified (Untested, Tested, Sampled)
- Incorrect identification of which Heating and Cooling Equipment Served by Duct System
- Incorrect Supply or Return Duct R-Value Identified
- Duct System Square Feet Served off by greater than 5%
-
of Return Grills off by 2 or more
- Duct Location or Supply/Return percentages listed as incorrect location (Attic, well vented vs Garage)
- Heating or Cooling Design Airflow modeled does not match value found in Manual J
- Supply and Return Duct Area if Measured or ACCA Manual D Sizing method is selected off by greater than 5%
- If Estimated method is selected but modeled values do not match Estimated values from software