FF_Q28_DuctLeakTestResults Version 7.1.1

Modified on Wed, 29 Jan at 5:20 PM

PHOTO REQUIRED of LTO Test Results per ANSI/RESNET/ICC 301-2019 APPENDIX B and MINHERS Chapter 9. If TDL result was used in place of LTO test result, then photo of TDL test results would be required in lieu of photo of LTO test results. Raters/RFIs are responsible for documenting reasons for missing photos. Duct leakage is tested according to ANSI/RESNET/ICC 380.

  • TDL has no energy effect on the RESNET model; LTO does have an energy effect.
  • Although many compliance programs allow TDL to be input into the software as LTO, and vice versa, documentation should represent which test was used.
  • Locations for the test (return register, return trunkline or airhandler, supply register or supply trunkline) should be documented and ideally reproduced for Field QA Review testing.

SCORING:

  • Satisfactory: Less than 10% variance between QAD result and Rater/RFI result
  • 1: 10% to less than 15% variance between QAD result and Rater/RFI result
  • 2: 15% to 25% variance between QAD result and Rater/RFI result
  • 3: Greater than 25% variance between QAD result and Rater/RFI result