Infiltration Help

Modified on Mon, 22 May, 2023 at 10:24 AM

Air Sealing


Infiltration Unit
The unit used to measure infiltration. For the infiltration value to be used in a confirmed HERS rating, a certified HERS rater must perform a Blower Door Test, mark it as tested in the Edit Design page and input the infiltration value in a unit other than ACH Natural. Otherwise, for the HERS rating, RESNET defaults will be used for the Rated Home.

Options include:
  • ACH at 50 Pa - The number of complete building air replacements that occur per hour during a blower door test at 50 Pa. Use total conditioned volume, including conditioned basements, to convert from CFM50. Blower Door testing procedures can be found in Chapter 8 of the RESNET Standards.
  • CFM at 50 Pa - Measured airflow in cubic feet per minute during a blower door test at 50 Pa. Blower Door testing procedures can be found in Chapter 8 of the RESNET Standards.
  • Effective Leakage Area - Also known as ELA, the area (in²) of a theoretical hole with rounded edges in the building envelope that would leak as much as all of the building's holes at a pressure difference of 4 Pa. Note that ELA is different from Equivalent Leakage Area (EqLA) which is the area of a sharp-edged theoretical hole at 10 Pa.
  • Specific Leakage Area - calculated by dividing ELA by the conditioned floor area in like units (i.e. in2/in2 or ft2/ft2).
  • ACH Natural - Estimate of building air changes per hour during typical conditions. This cannot be measured and therefore will be overridden by RESNET defaults when the HERS Index is calculated.
Shelter Class
  1. No obstructions or local shielding.
  2. Typical shelter for an isolated rural house.
  3. Typical shelter caused by other buildings across the street.
  4. Typical shelter for urban buildings on larger lots where sheltering obstacles are more than one building height away.
  5. Typical shelter produced by buildings or other structures immediately adjacent (closer than one house height): e.g., neighboring houses on same side of street, trees bushes, etc.

        * Descriptions from ASHRAE Handbook of Fundamentals 2009.
Measurement Type
  • Blower-door tested: Select this if the entered infiltration information reflects actual blower door test results according to testing protocol in RESNET Standards Ch. 8. This allows a confirmed HERS report to be printed, and the entered infiltration information will be used for the rated home when performing HERS calculations.
  • To be blower-door tested: Select this if the building will be blower door tested before applying for permits. This restricts you to only printing projected HERS reports, but allows you to see the impact of infiltration characteristics other than those generated for the HERS reference home.
  • Untested: Select this if the building will not be blower door tested. This allows a confirmed HERS report to be printed, but when performing HERS calculations the HERS reference home’s infiltration will be used for the rated home.
  • Threshold / Sampled: Choose this for both Threshold and Sampled ratings.
Infiltration Rate (Label will depend on Infiltration Unit)Enter the Infiltration Rate, appropriate for the Infiltration Unit you have selected, to be used for the energy and HERS calculation.

In accordance with RESNET/ANSI/ICC 380 (effective July 1, 2018), if a single point test has been completed, the resulting number must be multiplied by 1.1 before entering the value into Ekotrope.  Ekotrope will not make any modifications to the entered value, it will use it as-is for modeling.  Multi-point tests may be entered unmodified.


In Version 4.0.0 and later, only a compartmentalization test shall be used and no multiplier shall be applied. Ekotrope automatically adjusts the infiltration rate for the HERS and ERI rated homes as prescribed in RESNET/ANSI/ICC 301.


If the project you are modeling is in a version prior to 4.0:

In accordance with RESNET Guidelines for Multifamily Ratings (published in 2014), if an unguarded blower door test is performed on an attached dwelling unit that is not built on a slab and does not use corridor as ventilation supply air, then the blower door test result shall be multiplied by 0.85 before entering it into Ekotrope.


A guarded blower door test is performed with all interior adjacent spaces at the same pressure as the dwelling unit being tested.  By doing this it effectively measures the leakage to outside for the unit.  An unguarded (aka compartmentalization)  test means only the tested dwelling unit is pressurized, so it measures the total leakage of the unit.  Results from a compartmentalization test do not reflect where the leakage is coming from.

Field Test [CFM]Only visible if Measurement Type is Threshold / Sampled.

Enter the field test results in CFM50: Measured airflow in cubic feet per minute during a blower door test at 50 Pa.

For Threshold Ratings this should be entered, but is not required in order to submit to the RESNET Registry. For Sampled ratings, this should only be entered for the units that were actually tested in the field. In both cases, it is not used in the analysis, but it is reported to the RESNET Registry.


Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select at least one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article