Air Sealing
Infiltration Unit | The unit used to measure infiltration. For the infiltration value to be used in a confirmed HERS rating, a certified HERS rater must perform a Blower Door Test, mark it as tested in the Edit Design page and input the infiltration value in a unit other than ACH Natural. Otherwise, for the HERS rating, RESNET defaults will be used for the Rated Home. Options include:
|
Shelter Class |
|
Measurement Type |
|
Infiltration Rate (Label will depend on Infiltration Unit) | Enter the Infiltration Rate, appropriate for the Infiltration Unit you have selected, to be used for the energy and HERS calculation. In accordance with RESNET/ANSI/ICC 380 (effective July 1, 2018), if a single point test has been completed, the resulting number must be multiplied by 1.1 before entering the value into Ekotrope. Ekotrope will not make any modifications to the entered value, it will use it as-is for modeling. Multi-point tests may be entered unmodified. In Version 4.0.0 and later, only a compartmentalization test shall be used and no multiplier shall be applied. Ekotrope automatically adjusts the infiltration rate for the HERS and ERI rated homes as prescribed in RESNET/ANSI/ICC 301. If the project you are modeling is in a version prior to 4.0: In accordance with RESNET Guidelines for Multifamily Ratings (published in 2014), if an unguarded blower door test is performed on an attached dwelling unit that is not built on a slab and does not use corridor as ventilation supply air, then the blower door test result shall be multiplied by 0.85 before entering it into Ekotrope. A guarded blower door test is performed with all interior adjacent spaces at the same pressure as the dwelling unit being tested. By doing this it effectively measures the leakage to outside for the unit. An unguarded (aka compartmentalization) test means only the tested dwelling unit is pressurized, so it measures the total leakage of the unit. Results from a compartmentalization test do not reflect where the leakage is coming from. |
Field Test [CFM] | Only visible if Measurement Type is Threshold / Sampled. Enter the field test results in CFM50: Measured airflow in cubic feet per minute during a blower door test at 50 Pa. For Threshold Ratings this should be entered, but is not required in order to submit to the RESNET Registry. For Sampled ratings, this should only be entered for the units that were actually tested in the field. In both cases, it is not used in the analysis, but it is reported to the RESNET Registry. |
Was this article helpful?
That’s Great!
Thank you for your feedback
Sorry! We couldn't be helpful
Thank you for your feedback
Feedback sent
We appreciate your effort and will try to fix the article