Mechanical Ventilation Library Help
If you don't know the manufacturers specifications for ventilation systems, you can check the Home Ventilating Institute's Certified Products Directory.
Type | Options include:
| ||||||||||||||||
Ventilation Rate | Enter the mechanical ventilation rate in [Cubic Feet / Minute]. Reference ASHRAE Standard 62.2 for recommended ventilation rates. | ||||||||||||||||
Fan Watts | If the rated or measured wattage of the ventilation fan is known specify it here. If it isn't known, you may select the "Use Default Fan Watts" checkbox, which will satisfy RESNET Addendum 39. For Central Fan Integrated Systems (CFIS, aka Air Cyclers) without a supplemental fan, enter the wattage consumed by the air handler at the design ventilation rate. The design ventilation rate is not the full design flow of the air handler, it is the rate of controlled outside air for Indoor Air Quality. For Air Cyclers with a supplemental fan enter the wattage of the supplemental fan, not the air handler. From ANSI/RESNET Standard 301-2014 Addendum 39 To determine fan energy in the Rated Home, ventilation fan watts shall be based on the table below for the given system or the value observed in the Rated Home, for the highest airflow setting. Where needed to calculate fan watts, for systems other than Central Fan Integrated Supply (CFIS), the Whole-House Mechanical Ventilation System rate shall be assumed to be equal to Qfan, as calculated in accordance with Section 4.1.2 of ASHRAE Standard 62.2. For CFIS systems, the cfm used to determine fan watts shall be the larger of 400 cfm per 12 kBtu/h cooling capacity or 240 cfm per 12 kBtu/h heating capacity.
| ||||||||||||||||
Operational Hours per Day | Enter the number of hours the fan is running per day. | ||||||||||||||||
Runs Once Every Three Hours | This box should be checked if intermittent ventilation runs at least once every three hours. This will not affect the energy consumption or HERS Index of the home, but it will affect the ASHRAE 62.2 required ventilation calculation. ASHRAE 62.2 specifies a different ventilation effectiveness for fans that run at least once every 3 hours. |
If ERV or HRV are selected for type then the following field will also be available:
Energy Recovery Percent | Specify the Adjusted Sensible Recovery Efficiency (ASRE) of the ERV or HRV. If using the HVI directory, this will be in a row listed HEATING. If there are multiple rows, please select the ASRE with the corresponding temperature and fan flow that most closely reflects the climate and fan speed that will be present. |
Was this article helpful?
That’s Great!
Thank you for your feedback
Sorry! We couldn't be helpful
Thank you for your feedback
Feedback sent
We appreciate your effort and will try to fix the article